NOTICE!
Normally, non-conductive pollution occurs. Conductive pollution is unacceptable.
Conductive pollution can lead to the destruction of the device. The customer is re
-
sponsible for destructions, which were caused by pollution due to conductive materi-
als or components.
Technical Data
Instruction handbook BUM 60 / BUS 60
Document No.: 5.01032.05
27
of 82
3
3.4 Electrical data
3/6 3/6 - 54 -
x - xx6
6/12 6/12 - 54 -
x - xx6
8/16 12/24
Connection voltages
1)
3 x 400 - 480 V
AC
50 - 60 Hz, ± 10 %
Semiconductor fuses (external)
8)
16 A
Type of protection IP 20
Rated DC Link voltage
2)
540 V
DC
DC Link capacitor 110 µF 330 µF 110 µF 330 µF 220 µF 220 µF
Switch-on:
Ready for operation after
≥ 1,5 s
Frequency to switch on power sup-
ply
12)
unlimited
Output voltage
9) 10)
3 x 0 V
AC
... 95 % of input voltage
Output power
3) 10)
2 kVA 2 kVA 4,5 kVA 4,5 kVA 6 kVA 8 kVA
Typical motor power
3)
1,1 kW 1,1 kW 2,25 kW 2,25 kW 3 kW 4,5 kW
Rated output current
4) 5) 10) 11)
3 A
eff
3 A
eff
6 A
eff
6 A
eff
8 A
eff
12 A
eff
Peak output current
4) 5) 6) 10)
6 A
eff
6 A
eff
12 A
eff
12 A
eff
16 A
eff
24 A
eff
Low-voltage supply +24 V
DC
± 10 % (max. 55 W)
Ballast resistor R
B
(only BUM 60)
Peak power of ballast resistor
Continuos output
External ballast resistor
7)
10 kW / 1 s
250 W
min. 60 Ω
Max. switch-on time / ratio 1,5 s / 1 : 33
Power loss in rated operation,
without low-voltage supply,
without ballast
60 W 60 W 110 W 110 W 130 W 170 W
*
WARNUNG!
With a single-phase connection, neither of the two lines must have ground potential!