Start
No
Ye s
Mini-Calibrate
(‘CH -ve’ &
‘Reset’, then ‘ip’)
Page 8
Check
electrode
gap, gas
supply, etc.
‘000’
displayed
Press ‘ip’ &
‘CH +ve’ for
6 seconds
‘312’ will be
displayed for
7 minutes
Gas Type
check
starts
In 3 to 4
minutes
‘NG’ or
‘LPG’ is
displayed
No
Ye s
Check electrode
gap, gas supply,
etc.
Boiler
commissioned
Check boiler
temp has not
reached 85ºC
E133 or
other gas
error
displayed
Boiler will find
an ignition
curve to ignite,
briefly display
‘100’ then stop
When ‘000’
displayed restart
commissioning
(‘ip’ & ‘CH +ve’)
Mini-Calibration*
*It is referred to as Mini-Calibration
when activated whilst still in
commissioning mode. Only the
ignition curve is set then
‘000’ displayed.
See page 8
20.0 Commissioning Procedure & Errors