Product overview
EP1xxx32 Version: 2.5.0
2.9.2 EP1816-3008 - Technical data
Technical data EP1816-3008
Fieldbus EtherCAT
Fieldbus connection 2 x M8 socket (green)
Number of inputs 16
Input connections [}60]
25 pin SUB-D socket
Rated input voltage 24V
DC
(-15%/+20%)
Input filter 10µs
Signal voltage "0" -3...+5V (EN61131-2, type3)
Signal voltage "1" +11...+30V (EN61131-2, type3)
Input current typically 3mA (EN61131-2, type3)
Minimum cycle time > 500µs
Diagnostics Undervoltage detection <18V
DC
for Us and Up
Supply of the module circuitry From the control voltage Us
Current consumption of the module circuitry typically 120mA
Sensor supply From the control voltage Us
Current consumption of the sensors max. 0.5A, short-circuit-proof overall
Power supply connection Power supply: 1 x M8 plug, 4-pin
Onward connection: 1 x M8 socket, 4-pin
Electrical isolation Control voltage/fieldbus: yes
Permissible ambient temperature during operation -25°C ... +60°C
0 °C ... +55 °C (according to cULus, see UL
requirements)
Permissible ambient temperature during storage -40°C ... +85°C
Vibration/ shock resistance conforms to EN60068-2-6/ EN60068-2-27
EMC immunity/ emission conforms to EN61000-6-2/ EN61000-6-4
Protection class IP65, IP66, IP67 (according to EN60529)
Installation position variable
Technical approvals CE, cULus
Technical data Accelerometers
Sensor type Two 3-axis sensors / offset by 90°
Resolution 16bit raw data; 1mg / LSB
Measuring range ±2g/±4g/±8g/±16g configurable
Special features Self-test
Sampling rate 1Hz to 5kHz
Note
Maximum transfer rate
The EP1816-3008 reads sensors with sampling rates between 1Hz and 5kHz. Since the
smallest cycle time is limited to 500µs due to the internal processing, the resulting maxi-
mum transfer rate is 2.5kHz.