NOTE
In the example above, the device serial number was set to 12345. The filename
will then automatically be set to: BoX2ConfigSet_12345.json.
For a device without a serial number, the file should be named
BoX2ConfigSet.json. This is then a generic configuration file usable on any BoX2
device.
NOTE
The configuration files should be placed in the root folder of a USB flash drive
or SD card. If saving in C:\ root directory or in a not removable device, warnings
will show.
6. Eject the USB flash drive or SD card and connect it to your BoX2 device.
NOTE
A BoX2 device will load a configuration file only when a USB flash drive or SD
card is connected to the device. The device does not need to be rebooted.
Configuration files will be loaded in the following priority if several config files
are in root folder:
1. Device with a serial number matching a configuration file. The configuration
file with a serial number (in this example, BoX2ConfigSet_12345.json) is
loaded.
2. Device with a serial number not matching any configuration. Then the file
without a serial number (in this example, BoX2ConfigSet.json) is loaded.
When the BoX2 device has been updated, the LED changes temporarily to a red flash as confirmation.
Configuration