Additional Installation Tip s
7.7 CableandBusTerminationRS-485
If maximum transfer d istance and maximum transfer speed is needed,
shielded and twisted pair cable should be used. The mutual capacitance
may not exceed 52.5 pF/m, and the cable area should be at least 0.25 mm
2
(AWG 24).
0 V, the reference voltage for c ommunication should be included in
the cabling. With two-way communication use two pairs; one pair for
communication and one pair for 0 V.
The shield must be grounded at one end. The other end i s u sually grounded,
but with longer distances or when there is a difference in the ground potential,
theshieldshouldbeconnectedtothegroundvia0.F/250Vfilmcapacitor
to prevent ground current in the braided shield. A number of manufacturers
recommendthattheshieldbegroundedateachnode. Variousmanufacturers
have different systems for bus termination.
Depending on the recipients design, the bus wires may be on the same level or
require pull-up or pull-down to e nsure that no faulty signals are detected when the
bus i s in resting mode (all transmitters are disconnected).
7.8 USBMemorystick
TheUSBportsonX2basev2areof2.0standard. EventhoughUSB3.0maywork
well, we recommend to use USB memory sticks dedicated for USB 2.0.
BeijerElectronics, MAEN330
28

Other manuals for Beijer Electronics X2 base 7 v2 HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beijer Electronics X2 base 7 v2 HP and is the answer not in the manual?

Beijer Electronics X2 base 7 v2 HP Specifications

General IconGeneral
BrandBeijer Electronics
ModelX2 base 7 v2 HP
CategoryTouchscreen
LanguageEnglish

Related product manuals