16
V4. 12. 2010
.
Subject to modification
NMU230(-S/-F)
Technical data
Electrical data
AC 100...240V 50/60Hz
AC 85...265V
2.5W @ running / 0.6W @ holding
5.5VA
Cable 1m, 3x0.75mm
2
Functional data
10Nm
Selectable by switch
Max. 95
°
, adjustable by mechanical stops
150s for 95
°
Max. 35dB(A)
Mechanical, remote visible
Working conditions
IP54 in any direction
CE according to 89/336/EEC
Type 1 to EN 60730-1
-30...+50
°
C
-40...+80
°
C
95% RH, non-condensing (EN 60730-1)
Maintenance-free
Dimensions / weight
See 'Dimensions'
8x8mm
Min. 40mm (20mm with K-NA for reverse mounting - optional)
8...26.7mm (8...20mm with K-NA)
Approximately 800g
Dimensions [mm]
Cable 1m, 3x0.75mm
2
1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
124
06
2
6
25
99
41
08
NMU230(-S)
12418 16
8
3
26
25
99
41
32
102
0
3
0
8
2.5
8
NMU230-F
II (totally insulated)
CE according to 73/23/EEC
Gearing latch disengaged by pushbutton, self-resetting
Nominal voltage
Nominal voltage range
Power consumption
Wire/transformer sizing
Auxiliary switch
NMU230-S
Connection : Motor
Auxiliary switch NMU230-S
Torque
Direction of rotation
Manual override
Angle of rotation
Running time
Sound power level
Position indication
Protection class
Degree of protection
Low voltage directive
EMC
Ambient temperature
Mode of operation
Maintenance
Non-operation temperature
Humidity test
Shaft length
Dimensions (LxWxH)
NMU230-F
Weight
Shaft: NMU230(-S)
•ΓFor operation of air control dampers in HVAC system
•ΓTorque: 10Nm
•ΓNominal voltage: AC 100...240V
•ΓControl: Open/Close or 3-point