V4. 12. 2010
.
Subject to modification
31
Technical data
Electrical data
Nominal voltage
Power consumption
Power supply range
Wire/transformer sizing
5VA
Connection cable - Motor
Cable 1m, 3x0.75mm
2
Functional data
Torque - Motor
2Nm
Direction of rotation
Selectable by mounting L/R
Angle of rotation
Running time - Motor
Sound power level
75s
25s @ -20...50
°
C / max. 60s @ -30
°
C
Position indication
Service life
Working conditions
Protection class
Degree of protection
EMC
Mode of operation
Ambient temperature range
Non-operation temperature
Humidity test
Maintenance
Dimensions / weight
Dimensions (LxWxH)
Shaft length
Clamp down
Clamp up
Min. 84mm
Min. 20mm
Shaft diameter
6...12mm
Weight
Approximately 600g
- Spring return
- Spring return
Auxiliary switch TF24-S
1 SPDT, 1mA...3(0.5)A, AC 250V , adjustable
- Auxiliary switch TF24-S
Dimensions [mm]
Mechanical Fail-Safe Damper Actuator TF24(-S)
•ΓFor operation of air control dampers that perform safety function
•ΓTorque: 2Nm
•ΓNominal voltage: AC/DC 24V
•ΓControl: Open/Close
•ΓIntegrated auxiliary switch (TF24-S)
84
6...12
104
8420 36
61
77
176
AC 24V 50/60Hz, DC 24V
2.5W @ running / 1.5W @ holding
AC 19.2...28.8V, DC 21.6...28.8V
Cable 1m, 2x0.75mm
2
2Nm @ nominal voltage
Max. 95
°
, 37...100% adjustable by mechanical stops
Motor max. 50dB(A), Spring approximately 62dB(A)
Mechanical
> 60,000 full cycles
III (safety extra-low voltage)
IP42 in any direction
CE according to 89/336/EEC
Type 1. AA to EN 60730-1
-30...+50
°
C
-40...+80
°
C
95% RH, non-condensing (EN 60730-1)
Maintenance-free
140x77x84mm