32
4. 12. 2010
.
Sub
ect to modification
Technical data
Electrical data
AC 24V 50/60Hz
2.5W @ running / 1W @ holding
AC 19.2...28.8V
4VA
Cable 1m, 4x0.75mm
Functional data
2Nm @ nominal voltage
2Nm
Selectable by mounting L/R
Max. 95
°,
37...100% adjustable by mechanical stops
Motor max. 35dB(A), Spring approximately 62dB(A)
150s ( 0...2Nm)
25s @ -20...50°C/max. 60s @ -30
°
C
Mechanical
> 60,000 full cycles
Working conditions
III (safety extra-low voltage)
IP42 in any direction
CE according to 89/336/EEC
Type 1. AA to EN 60730-1
-30...+50
°
C
-40...+80
°
C
95% RH, non-condensing (EN 60730-1)
Maintenance-free
Dimensions / weight
140x77x84mm
Min. 84mm
Min. 20mm
Approximately 600g
Dimensions [mm]
Mechanical Fail-Safe Damper Actuator TF24-3
6...12mm
Nominal voltage
Nominal supply range
Power consumption
Wire/transformer sizing
Connection : Motor
Torque - Motor
- Spring return
- Spring return
Direction of rotation
Angle of rotation
Running time - Motor
Sound power level
Position indication
Service life
Protection class
Degree of protection
EMC
Ambient temperature
Mode of operation
Maintenance
Non-operation temperature
Humidity test
Shaft length Clamp up
Clamp down
Dimensions (LxWxH)
Weight
Shaft diameter
•ΓFor operation of air control dampers that perform safety function
•ΓTorque: 2Nm
•ΓNominal voltage: AC 24V
•ΓControl: 3-point
84
61 176
77
20 84
104
6...12
36