ISOSCAN® EDS440 and EDS441
Live conductors and measuring current transformers
Ensure that all live conductors are routed through the measuring current transformer. Do not route
any existing PE conductors or shields of shielded cables through the measuring current transformer!
Standard measuring current transformers are not suitable for the EDS44… system and must not be used.
An accurate measurement result can only be obtained when these instructions are observed.
For further information regarding measuring current transformers, refer to the respective data sheets.
EDS44x_D00201_10_M_XXEN/11.2023 25