ISOSCAN® EDS440 and EDS441
Screw fixing 2 × M4 with mounting clip
Enclosure material polycarbonate
Flammability class UL 94 V-0
Dimensions in mm (W × H × D) 72 × 93 × 63
Weight
EDS44…-S approx. 122 g
EDS44…-L, …-LAB, …-LAF approx. 242 g
“W” option data deviating from the standard version
Devices with the suffix “W” feature increased shock and vibration resistance. The electronics is covered with a
special varnish to provide increased protection against mechanical stress and moisture.
Ambient temperatures
Operating temperature −40…+70 °C
Transport −40…+85 °C
Long-term storage −25…+70 °C
Climatic conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) 3K23
Mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) 3M12
12.2 Standards and certifications
Observe the applicable national and international standards.
The EDS44… series meets the device standards:
DIN VDE 0100-410 (VDE 0100-410)
DIN EN 61557-9 (VDE 0413-9)
IEC 61557-9
DIN EN 50155 (VDE 0115-200)
DIN EN 45545-2:2016
Subject to change! The specified standards take into account the edition valid until 08/21 unless otherwise
indicated.
The operating manuals for the individual system components provide you with information about the
standards that apply to that particular device.