Bender ISOSCAN W Series - Alarm Messages; Insulation Fault (ALARM IΔL )

Bender ISOSCAN W Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Display and alarm messages
-1
>3s
ADDR.
RESET
+1
+10
TEST
CHANNELS / ADDR.
12
11109
87
345621
+10 +20 +40
Addr. Mode
n
I
ALARM
L
I
ALARM
SERVICE
COM/ADDR.
ON
5.4 Alarm messages
The EDS44…-L indicates the alarm messages on its control panel.
The EDS44…-S indicates the alarm messages on the ISOMETER®.
Possible causes of an alarm message are:
Insulation fault
residual current exceeded
device error
measuring current transformer fault
measuring current transformer connection fault
interference
5.4.1 Insulation fault (ALARM I
ΔL
)
If an insulation fault is detected on a measuring channel (EDS function), the “ALARM I
ΔL
” LED (main alarm) and
the LED of the channel on which the fault was detected, light up.
-1
>3s
ADDR.
RESET
+1
+10
TEST
CHANNELS / ADDR.
12
11109
87
345621
+10 +20 +40
Addr. Mode
n
I
ALARM
L
I
ALARM
SERVICE
COM/ADDR.
ON
In addition, the fault is indicated on the display of the ISOMETER®.
34 EDS44x_D00201_10_M_XXEN/11.2023