ISOSCAN® EDS440 and EDS441
When mounting the measuring current transformers any magnetic fields nearby that could cause
interference are taken into account.
When the addresses of the BS bus nodes were set, no address was assigned twice. The ISOMETER® with
integrated locating current injector (e.g. ISOMETER® iso685-D-P) is set as master.
6.3 Switching on
1. Switch on the supply voltage of all devices connected to the BS bus or the BB bus.
u
The “ON” LED of the EDS44… flashes at first and then lights up continuously.
2. Eliminate all displayed insulation faults and device errors via the ISOMETER®. If the response values for
prewarning and main alarm are exceeded, the the EDS44…-L indicates the respective alarm message by
lighting up the alarm LED “ALARM I
ΔL
” or “ALARM I
Δn
” (see “Alarm messages”, page 56).
Further information regarding fault messages on the EDS44… can be displayed via the ISOMETER®.
Device errors may be caused by measuring current transformers not being connected. Check the
measuring current transformer connections. Disconnect the channels that are not required in the menu
of the ISOMETER®.
Pending alarm messages may temporarily not be available due to synchronisation processes on the BS
bus. However, if the cause of the alarm persists, the alarm messages reappear after a few seconds.
6.4 Steps for commissioning ISOMETER® and EDS
Commissioning scheme iso685-…-P mit EDS44…
Commissioning ISOMETER® Commissioning EDS Commissioning
ISOMETER® with EDS
1 Connect device according to
wiring diagram and device
documentation.
Connect device and measuring
current transformer according
to wiring diagram and device
documentation.
Switch off the supply voltage of all
devices.
2 Switch on supply voltage. Switch on supply voltage. Connect EDS to ISOMETER®
EDS44…-L via BS bus
EDS44…-S via BB bus
3 Switch on mains voltage. The ON LED flashes during power
up until the device is ready for
operation.
Switch on supply voltage of all
devices.
4 Run commissioning wizard. Set BS address with the ADDR
button of the EDS44…-L. Display by
channel LEDs
Set EDS mode in the ISOMETER ®
menu:
EDS > General > Modus
5 Run self test of the ISOMETER®. Eliminate all possible device errors
in accordance with the device
documentation.
Search for configurable measuring
channels in the ISOMETER® menu:
EDS > Scan channels