ISOSCAN® EDS440 and EDS441
11.1.9 Response values of EDS440-LAF for DC systems
System leakage capacitance of max. 100 μF
Nominal voltage Max. insulation fault R
F
DC 60 V 2 kΩ
DC 110 V 5 kΩ
DC 220 V 10 kΩ
DC 300 V 15 kΩ
DC 600 V 30 kΩ
DC 1000 V 50 kΩ
11.1.10Response values of EDS440-LAF for AC systems
System leakage capacitance of max. 100 μF
Nominal voltage Max. insulation fault R
F
1AC 110 V 2 kΩ
1AC 230 V 5 kΩ
1AC 400 V 10 kΩ
3AC 230 V 15 kΩ
3AC 400 V 25 kΩ
3AC 500 V 30 kΩ
3AC 690 V 40 kΩ
EDS44x_D00201_10_M_XXEN/11.2023 71