Alarm messages
10 Alarm messages
Alarm message Description Measures
“ALARM I
ΔL
” LED
lights up
Channel LED lights
up
The response value of the
insulation level is exceeded on
one channel.
Determine cause of the insulation fault and eliminate
it.
See “Insulation fault (ALARM I
ΔL
)”, page 34.
“ALARM I
Δn
” LED
lights up
Channel LED lights
up
The response value of the
residual current is exceeded on
one channel.
Determine cause of the exceeded residual current and
eliminate fault.
See “Residual current exceeded (ALARM I
Δn
)”, page 35.
“SERVICE” LED
lights up
Internal device error enum-title
Press the TEST button
Switch the supply voltage off and on
Read out error code on the ISOMETER®
Contact Bender service
See “Connection fault of the current transformers”,
page 35.
“SERVICE” LED
lights up
Channel LED
flashes
Connection fault of the current
transformers Possible causes:
Measuring current
transformers defective
Power supply cable
interrupted
Power supply cable short-
circuited
Replace defective measuring current transformers
Check cables
See “Connection fault of the current transformers”,
page 35.
Channel LED
flashes
Interferences during
measurement Possible causes:
Low-frequency residual
currents
External magnetic fields
Identify interference sources and eliminate them
If several alarm messages appear at a time, the indication changes correspondingly. In this case, the alarm
LED and the channel LED of the faulty channel light up together for approx. two seconds.