ISOSCAN® EDS440 and EDS441
EDS44…-L and -S:
Press TEST button on the ISOMETER®.
The EDS44…-L responds as follows:
LEDs “COM/ADDR.” and “SERVICE” light up.
All alarm relays switch (function can be deactivated).
An alarm message is sent on the BS bus.
An entry with the suffix “TEST” is stored in the history memory of the ISOMETER®.
All active channel LEDs light up.
-1
>3s
ADDR.
RESET
+1
+10
TEST
CHANNELS / ADDR.
12
11109
87
345621
+10 +20 +40
Addr. Mode
n
I
ALARM
L
I
ALARM
SERVICE
COM/ADDR.
ON
After the test, only the “ON” LED must light up.