Technical data
Supply voltage
Supply voltage range U
s
EDS44...-L (…-LAB, …-LAF) AC/DC 24…240 V
Supply voltage range U
s
EDS44...-S DC 24 V
Tolerance of U
s
−20…+15%
Frequency range of U
s
DC, 50…400 Hz
1)
2)
Tolerance: −5…+15 %
Power consumption, typically 50 Hz (400 Hz) EDS44...-L ≤4 W / 7 VA (≤4 W, 28 VA)
Power consumption, typically (DC via BB bus) EDS44...-S ≤1 W
1) At a frequency > 200 Hz, the connection of X1 and k1-12/l1-12 must be insulated. Only permanently installed devices
which at least have overvoltage category CAT2 (300 V) may be connected.
2) Only 50/60 Hz are permitted for UL applications.
Response values
EDS440 EDS441
Response value for insulation fault location (I
ΔL
) 2…10 mA 0.2…1 mA
Relative uncertainty (I
ΔL
)
3)
±30 %, min. ±2 mA ±30 %, min. ±0.2 mA
Response value for residual current measurement (I
Δn
) 0.1…10 A 0.1…1 A
Relative uncertainty (I
Δn
) 42…60 Hz ±5 % ±5 %
Relative uncertainty (I
Δn
) 61…1000 Hz −20…0 % −20…0 %
Hysteresis 20 % 20 %
3) Residual current effect of > 100 mA results in a greater relative uncertainty.
Time response
Scanning time for all channels for insulation fault location (I
ΔL
) profile-dependent, min. 6 s
Response time for residual current measurement (I
Δn
) ≤ 400 ms
Response time for measuring current transformer monitoring max. 18 min
Measuring circuit
Nominal system voltage U
n
EDS440 refer to locating current injector
(e.g. ISOMETER® iso685-D-P)
Nominal system voltage U
n
EDS441 AC 230 V ±15 %
DC 220 V ±40 %
External measuring current transformers for EDS440 W…, WR…, WS…
External measuring current transformers for EDS441 W…/8000, WS…/8000
External measuring current transformers for EDS441-LAB CTUB102