2) PROGRAMMING
The various functions of the control unit can be programmed by using the LCD display provided on the side of the unit and by setting the desired
values on the Programming Menu, as described hereunder.
The Parameters Menu allows for the presetting of a digit value to a function, like an adjustment trimmer.
The Logic Menu allows for the activation and deactivation of a function, like the setting of a Dip-Switch.
The special functions follow the Parameters Menu and the Logic Menu and can vary according to the type of control unit or software review.
To access programming :
1 – Press the <PG> push-button, the first Parameters Menu “PAR” appears on the display.
2 – Select the desired menu by using the <+> or <-> keys (PAR>>LOG>>NMAN>>RES>>PAR>>....).
3 – Press the <PG> push-button, the display shows the first function available in the Menu.
4 – By using the <+> or <-> keys select the function to be modified.
5 – Press the <PG> push-button, the currently preset value for the selected function is displayed.
6 – By using the <+> or <-> keys, select the value which is to be assigned to the function.
7 – Press the <PG> push-button and the “PRG” message is displayed. This means that programming has been completed.
Note:
The <+> e <-> push-buttons, when the unit is not in programming mode, perform the OPEN and CLOSE function, respectively, in service man
mode (the buttons should be kept pressed for the entire duration of the operation).
When upon a Function Menu, press keys <+> e <-> simultaneously to pass to higher menu without making any change.
When the unit is switched on, the Software version is displayed for around 2sec.
Keep either keys <+> or <-> pressed to speed up the increase/decrease of values.
After 60 sec wait, the control unit exits the Programming mode and the display switches off.
3) PARAMETERS, LOGIC AND SPECIAL FUNCTIONS
In the tables hereunder the single functions available in the control unit are shown.
PARAMETERS (PAR)
MENU FUNCTION
MIN-MAX-
(Default)
MEMO
TCA
Automatic closure time. Active with logic “TCA”= ON only.
At the end of the preset time, the control unit sends a closure control signal.
1-240-(40s)
TM
Motor operating time. The operation time is adjusted during the opening and closing phases of the motor.
5-240-(60s)
Tped
The stroke time of the gate leaf is adjusted during the partial opening phase (pedestrian mode).
In the motors with encoder, the value is expressed in percentage. In motors without encoder
the value is expressed in seconds.
5-100-(20)
TLS
The activation time of the courtesy light is adjusted. The contact closes with the beginning of
the opening operation. The time counting starts only with gate completely closed.
1-240-(60s)
AUX1
Select the operating mode of the auxiliary output 9/10 AUX1 (Free Contact N.O.)
0: Open gate warning (SCA), indicates gate status: closed contact when gate open, open con-
tact when gate closed, intermittent during operation (fig. 3, SCA)
1: Second preset receiver radio channel (see fig. 3, II°CH RADIO and radio menu - 2CH)
2: Courtesy light, the duration of the contact closure is adjustable by the TLS parameter (fig.3
SERVICE LIGHT/ZONE LIGHT).
3: Zone light: the contact closes for the duration of the operation and for the duration of the
TCA, it opens again when the gate is closed.
0-3-(2)
* WARNING:
An incorrect setting of these parameters may cause danger. Please comply with regulations in force!
LOGIC (LOGI)
MENU FUNCTION
ON-OFF-
(Default)
MEMO
TCA
The automatic closure is enabled or disabled.
Off: disabled automatic closure.
On: enabled automatic closure.
(OFF)
IbL
The multi-flat function is enabled or disabled.
Off: disabled multi-flat function.
On: enabled multi-flat function. The P.P. (Step-by-step) impulse or the impulse of the transmitter
has no effect in the opening phase.
(OFF)
IBCA
Enables or disables the condominium function during TCA counting.
On: condominium function enabled. The PP or transmitter pulse has no effect during TCA counting.
Off: condominium function disabled.
(OFF)
SCL
The rapid closure is enabled or disabled.
On: enabled rapid closure. With open gate or gate in the opening phase, the activation of the
photocell causes the automatic closure of the gate 3 sec after its activation. This function is
enabled only with TCA:ON
Off: rapid closure disabled.
(OFF)
PP
The operating mode The operating mode of the “P.P.” (Step-by Step) button and of the transmitter
is selected.
Off: Operation: OPEN > STOP > CLOSE > STOP >
On: Operation : OPEN > CLOSE > OPEN >
(OFF)