2.3 Environmental Conditions
2.4 Altitude Derating
Benshaw controllers are capable of operating at altitudes up to 3,300 feet (1000 meters) without requiring
altitude derating. Table 6 provides the derating percentage to be considered when using a controller above
3,300 feet (1000 meters).
For derating above 10,000 feet consult Benshaw Inc.
2.5 Approvals
The MX
2
SEP Control Card is UL, cUL Recognized
2.6 Certificate of Compliance
CE Mark, see Appendix D on Page 117.
Table 3: Environmental Ratings
Operating Temperatures
–10°C to +40°C (14°F to 104°F) enclosed
–10°C to +50°C (14°F to 122°F) open
Storage Temperatures –20°C to +70°C (–4°F to 155°F)
Humidity 0% to 95% non condensing
Altitude 1000m (3300ft) without derating
Maximum Vibration 5.9m/s
2
(19.2ft/s
2
) [0.6G]
Cooling Natural convection (Fans optional)
Table 4: Altitude Derating
Altitude
Percent Derating
(Amps)
3300 Feet 1006 meters 0.0%
4300 Feet 1311 meters 3.0%
5300 Feet 1615 meters 6.0%
6300 Feet 1920 meters 9.0%
7300 Feet 2225 meters 12.0%
8300 Feet 2530 meters 15.0%
9300 Feet 2835 meters 18.0%