EasyManuals Logo

Beretta Ciao 25C User Manual

Beretta Ciao 25C
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
put the ramp of the gas valve back in place and screw the nut
reposition the previously removed components
power up the boiler and open the gas tap again.
Adjust the boiler as explained in paragraph “3.9 Adjustments” and paragraph
“3.10 Gas valve calibration”
.
b
Conversion must be carried out by qualified personnel.
b
After the transformation, apply the new rating plate included in the kit.
3.12 Range rated
Thisboilercanbeadaptedtotheheatingrequirementsofthesystem,infactit
is possible to set the maximum delivery for heating operation of the boiler itself:
power up the boiler
set the parameter
310 Range rated
Set the maximum heating value (rpm) and confirm.
007
.
rpm
007
.
rpm
confirm
MAX
rpm
Record the new set value in the table on the back cover of this manual. For
subsequentcontrolsandadjustments,refertothesetvalue.
b
The calibration does not entail the ignition of the boiler.
The boiler is supplied with the adjustments shown in the technical data table.
Depending on plant engineering requirements or regional flue gas emission
limitshowever,thisvaluecanbemodifiedbyreferringtothegraphsbelow.
1000
1400
1800
2200
2600
3000
3400
3800
4200
4600
5000
5400
5800
6200
6600
7000
7400
7800
8200
8600
9000
2 4 6 8 10 12 14 16 18 20 22 24 26
Giri venlatore (r.p.m.)
Portata termica (kW)
Heat input curve - fan rotations - Ciao 25C f
fan rotations (r.p.m.)
heat input (kW)
fan rotations (r.p.m.)
1000
1400
1800
2200
2600
3000
3400
3800
4200
4600
5000
5400
5800
6200
6600
7000
7400
7800
8200
8600
9000
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32
Giri venlatore (r.p.m.)
Portata termica (kW)
Caldaia CIAO 30C f
Heat input curve - fan rotations - Ciao 30C f
heat input (kW)
3.13 Faults and reporting
Ifthereisafault,anerrorcode“Axx”isshownonthedisplay.
Incertaincases,theerrorcodeisaccompaniedbyanicon:
FAULTS ICONS DISPLAYED
amefailureA10
allfaultsexceptamefailureandwaterpressure
water pressure
Reset function
Toresetboileroperationintheeventofafault,press
:
> 2 sec
Res
Ifthecorrectoperatingconditionshavebeenrestored,theboilerwillstartup
again automatically
.
Inthepresenceofaremotecontrol,amaximumof5consecutiveunlocking
attempts are available.
Inthiscase,bypressing the boiler restores the initial attempts.
b
Iftheattemptstoresettheboilerdonotwork,contacttheTechnicalAs-
sistance Centre.
Fault A41
Ifthepressurevaluefallsbelowthe0.3barsafetyvalue,theboilershowsthe
fault code A41 for a transitory time of 10 min. If the fault still persists after this
time,faultcodeA40 will appear.
4
A
1 4
A
0
With fault A40 on the boiler it is necessary to:
- openthellingtap(A) turning it counterclockwise
- access the Info menu (
“4.3 INF
O menu ”,itemI018),tocheckthatthe
pressure value reaches 1-1.5 bar
- close thellingtap(A),makingsureyouhearthemechanicalclick.
A
Press to restore operation. Afterfilling,runaventingcycle.Ifthepressure
dropisveryfrequent,contacttheTechnicalAssistanceCentre
.
Fault A60
Theboilerisworkingnormally,butdoesnotprovideanystabilityofthedomestic
hotwatertemperaturethat,inanyevent,issuppliedatatemperatureofaround
50°C. The intervention of the Technical Assistance Centre is required.
Fault A91
The boiler has a self-diagnosis system that signals the need to clean the primary
heat exchanger on the basis of the total number of hours in certain operating
conditions (alarm code A91).
Fault A91 occurs when the counter exceeds the value of 2500 hours; this value
can be checked in the “4.3 INFO menu ”,itemI015(visualization/100,
example 2500h = 25)
Aftercleaning(usingthespecialkitsuppliedasanaccessory),resetthetotal
hours counter by bringing parameter 312 = 1.
NOTE: The meter resetting procedure should be carried out after each in-dep-
th cleaning of the primary exchanger or if this latter is replaced.
3.14 Replacing the board
Ifthecheckandadjustmentboardisreplaced,itmaybenecessarytorepro-
gramtheconfigurationparameters.Inthiscase,refertotheparameterstable
toseetheboarddefaultvalues,thefactorysetvalues,andthepersonalised
values
.
The parameters that must be checked and reset if necessary after repla-
cing the board are
: 301 - 302 (SERVICE) - 306 - 307 - 308 - 309 - 310.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beretta Ciao 25C and is the answer not in the manual?

Beretta Ciao 25C Specifications

General IconGeneral
BrandBeretta
ModelCiao 25C
CategoryBoiler
LanguageEnglish

Related product manuals