EasyManuals Logo
Home>Beretta>Boiler>Ciao 25C

Beretta Ciao 25C User Manual

Beretta Ciao 25C
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
7
In particular on the boiler display:
- it is no longer possible to set the boiler OFF/WINTER/SUMMER status (it is
set by the OT+ remote control)
- it is no longer possible to set the domestic hot water setpoint (it is set by the
OT+ remote control)
- the combination of the A+B keys remains active for the setting of the DOME-
STIC HOT WATER COMFORT function
- the domestic hot water setpoint (I005) is displayed in the INFO menu
- the heating setpoint value calculated by the OT+ remote control (I017) is
displayed in the INFO menu
- the heating setpoint set on the boiler display is used only if there are heat
requests from the TA and the OT+ remote control does not have a request if
the parameter: 311 = 1 or 311 = 0,butthe VZONE jumper on the adjustment
board is closed. This value is displayed in the INFO menu (I016)
.
- to activate the “Combustion analysis” function with an OT+ remote control
connected,youmusttemporarilydisabletheconnectionbysettingthepa-
rameter 803 = 0 (SERVICE); remember to reset this parameter once the
functionhasnished.
Key 3 remains active for the visualisation of the INFO menu and the enabling
of the SETTINGS menu.
High voltage connections
The connection to the mains supply must be made via a separation device
with an omnipolar opening of at least 3.5 mm (EN 60335/1 - category 3). The
applianceworkswithalternatingcurrentat230Volt/50Hz,andisincompliance
with Standard EN 60335-1. It is obligatory to make the connection with a safe
ground/earth,incompliancewithcurrentdirectives.
b
The installer is responsible for ensuring the appliance is suitably earthed;
the manufacturer will not be liable for any damage resulting from an in-
correct or absent earth connection.
b
It is also advisable to respect the phase-neutral connection (L-N).
b
The earth conductor must be a couple of cm longer than the others.
b
To create the seal of the boiler use a clamp and tighten it on the cable
grommet used.
The boiler can operate with a phase-neutral or phase-phase power supply. It
is forbidden to use gas and/or water pipes to earth electrical appliances. Use
the power cable supplied to connect the boiler to the mains power supply. If the
powercablehastobereplaced,useaHARH05V2V2-F,3x0.75mm²cable,
Ø max external 7 mm.
2.5 Gas connection
The connection of the gas supply must be carried out in compliance with current
installationstandards.Beforecarryingouttheconnection,checkthatthetypeof
gas is that for which the appliance is set up
.
2.6 Removing the casing
Toaccessthecomponentsinside,removethecasingasshowninthegure.
b
Ifremovingthesidepanels,putthembackintheirinitialposition,referring
to the adhesive label on its wall
.
b
If the front panel is damaged it must be replaced
.
b
The noise absorbing panels inside the front and side walls ensure the
airtight seal for the air supply duct in the installation environment
.
b
It is therefore CRUCIAL after the dismantling operations to correctly re-
positionthecomponentstoensuretheboilerssealise󰀨ective
.
A
B
B
C
C
2.7 Flue gas exhaust and combustion air suction
Toevacuatethecombustionproducts,refertoUNI7129-7131.Alwayscomply
withlocalstandardsoftheFireDepartment,theGasCompanyandwithpossi-
ble municipal dispositions.
Itisessentialfortheevacuationoftheuegasesandtheadductionoftheboi-
lers combustion air that only original pipes be used (except C6) and that the
connectionismadecorrectlyasshownintheinstructionsprovidedwiththeue
gases accessories
.
Asingleuecanbeconnectedtoseveralappliancesprovidedthateveryap-
pliance is the condensing type.
b
b
“Straightlength”meansfreeofbends,andincludesterminalsandjoints.
b
Theboilerissuppliedwithouttheuegasexhaust/airsuctionkit,sinceit
ispossibletousetheaccessoriesforcondensingappliancesthatbestt
the installation characteristics (see catalogue
).
b
Themaximumlengthsofthepipesrefertotheueaccessoriesavailable
in the catalogue
.
b
Itiscompulsorytousespecicpipes
.
b
Thenoninsulateduegasoutletpipesarepotentialsourcesofdanger
.
b
The use of a longer pipe causes a loss of output of the boiler
.
b
The exhaust pipes can face in the direction most suited to the installation
requirements
.
b
Asenvisagedbycurrentlegislation,theboilerisdesignedtotakeinand
disposeofuegascondensateand/ormeteoricwatercondensatederi-
vingfromtheuegasdischargesystemusingitsownsiphon
.
b
If a condensate relaunch pump is installed, check the technical data
(providedbythemanufacturer)regardingoutput,toensureitoperates
correctly
.
- Positionthedischargepipesothattheconnectionsitsfullyupagainsttheue
gases turret of the boiler.
- Afterpositioningit,makesurethe4notches(A) slip into the groove (B).
- Fully tighten the screws (C)thatholdthetwoangelockingterminals,sothe
bend itself is restrained held in place.
A
A
C
C
B
Ø80-125
B
B
B
B
B23P-B53P Ø60-100 Ø80-80
b
If the Ø 60-100 to Ø 80-80 splitter kit is used instead of the twin pipe
system,thereisalossinthemaximumlengthsasshowninthetable
.
Ø 50 Ø 60 Ø 80
Loss of length (m) 0,5 1,2
5,5foruegasespipe
7,5forairpipe
Twin pipes with Ø 80 pipework (Ø50 - Ø60 - Ø80)
Thankstotheboilercharacteristics,aØ80uegasexhaustpipecanbecon-
nected to the Ø50 - Ø60 - Ø80 piping ranges.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beretta Ciao 25C and is the answer not in the manual?

Beretta Ciao 25C Specifications

General IconGeneral
BrandBeretta
ModelCiao 25C
CategoryBoiler
LanguageEnglish

Related product manuals