EasyManuals Logo
Home>Beretta>Boiler>Ciao 25C

Beretta Ciao 25C User Manual

Beretta Ciao 25C
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
8
b
Forthepipe,youareadvisedtomakeaprojectcalculationinorderto
respect the relevant regulations in force.
Thetableshowsthestandardcongurationsallowed
.
Air suction
1 bend 90° Ø 80
4.5m pipe Ø80
Flue gas
discharge
1 bend 90° Ø 80
4.5m pipe Ø80
Reduction from Ø80 to Ø50 from Ø80 to Ø60
Fluebasebend90°,Ø50orØ60orØ80
For ducting pipe lengths see table
The boilers are factory set to:
CH rpm DHW rpm Max length pipes (m)
Ø50 Ø60 Ø80
model A
7.000 8.700
6 19 95
1 9 45
model B
7.000 8.700 4 16 80
7.400 8.700 0 7 35
Shouldgreaterlengthsberequired,compensatethepressuredropwithanin-
creaseinther.p.m.ofthefan,asshownintheadjustmentstable,toprovidethe
rated heat input,referring to paragraph
“3.9 Adjustments”
.
b
Theminimumcalibrationshouldnotbemodied.
b
Incaseofnewfanspeedadjustment,carryouttheCO2 check procedu-
re as indicated in paragraph “3.8 Combustion analysis”.
Adjustment tables INSIDE CHIMNEY PIPES
twin ue pipe
Fan rotations rpm Pipes Ø50 Pipes Ø60 Pipes Ø80 ∆P at boiler outlet
CH DHW Maximum length (m)
model A
7.000 8.700 6 19 95 180
7.100 8.800 12 * 33 * 165 * 260
7.200 8.900 16 * 39 * 195 * 300
7.300 9.000 19 * 46 * 230 * 342
7.400 9.100 23 * 53 * 265 * 383
7.500 9.200 27 * 61 * 305 * 431
7.600 9.300 29 * 67 * 335 * 465
7.700 9.400 32 * 73 * 365 * 500
model B
7.000 8.700 4 16 80 180
7.100 8.800 8 * 26 * 130 * 260
7.200 8.900 11 * 32 * 160 * 300
7.300 9.000 14 * 38 * 190 * 342
7.400 9.100 17 * 44 * 220 * 383
7.500 9.200 19 * 50 * 250 * 431
7.600 9.300 22 * 56 * 280 * 465
7.700 9.400 25 * 62 * 310 * 500
(*) Maximum length that can be installed ONLY with class H1 discharge pipes.
compact twin ue pipe
Fan rotations rpm Pipes Ø50 Pipes Ø60 Pipes Ø80 ∆P at boiler outlet
CH DHW Maximum length (m)
model A
7.000 8.700
1
9 45 180
7.100 8.800
7 *
23 *
115
* 260
7.200 8.900
11 *
29 *
145
* 300
7.300
9.000 14 *
36 *
180
* 342
7.400
9.100 18 *
43 *
215
* 383
7.500
9.200 22 *
51 *
255
* 431
7.600
9.300 24 *
57 *
285
* 465
7.700
9.400 27 *
63 *
315
* 500
model B
7.400 8.700 0 7 35 190
7.500
8.800
4 *
17 *
85
* 256
7.600
8.900
7 *
23 *
115
* 300
7.700
9.000
10 *
29 *
145
* 340
7.800
9.100
13 *
35 *
175
* 380
7.900
9.200
15 *
41 *
205
* 417
8.000
9.300
18 *
47 *
235
* 458
8.100
9.400
21 *
53
* 265
* 500
(*) Maximum length that can be installed ONLY with class H1 discharge pipes.
TheØ50orØ60orØ80congurationscontainLabtestdata.Intheeventof
installationsthatdi󰀨erfromtheindicationsinthe“standardcongurations”and
“adjustments”tables,refertotheequivalentlinearlengthsbelow.
b
Inanycase,themaximumlengthsdeclaredinthebookletareguarante-
ed,anditisessentialnottoexceedthem.
COMPONENT Linear equivalent in metres Ø80 (m)
Ø 50 Ø 60
Bend 45° 12,3 5
Bend 90° 19,6 8
Extension 0.5m 6,1 2,5
Extension 1.0m 13,5 5,5
Extension 2.0m 29,5 12
chimney for ducting
ø 50 mm or ø 60
mm or ø 80 mm
length
90° bend ø 50
mm ø 60 mm
or ø 80 mm
80-60 mm or
ø 80-50 mm
reduction
90° bends ø 80 mm
4,5m Ø 80mm
4,5m Ø 80mm
°
C
508
.
2.8 Filling the heating system and eliminating air
C
A
NOTE: llthesystemviathellingtap(A) making sure the boiler is electrically
powered.
NOTE:eachtimetheboilerispoweredup,theautomaticventingcycleiscar-
ried out.
NOTE: the presence of a water alarm (A40,A41orA42) does not allow the
venting cycle to be carried out.
Fill the heating system as follows:
- openthellingtap(A) turning it counterclockwise
- then access the Info menu (
“4.3 INF
O menu ”,itemI018),tocheck
that the pressure value reaches 1-1.5 bar
.1
5
.
NOTE: ifthemainspressureislessthan1bar,keepthellingtap(A) open
during the venting cycle. Close it when the cycle has ended.
To start the venting cycle:
- switcho󰀨theelectricalsupplyforafewseconds
- connectthepoweragain,leavingtheboilerOFF
- check that the gas tap is closed.
At the endofthecycle,ifthecircuitpressurehasdropped,openthellingtap
(A) again to bring the pressure back up to the recommended value (1-1.5 bar).
The boiler is ready after the vent cycle.
- Remove any air in the domestic system (radiators, zone manifolds, etc.)
using the bleed valves.
- Once again check that the system pressure is correct (ideally 1-1.5 bar) and
restore the levels if necessary.
- Ifairisnoticedwhenoperating,repeattheventcycle.
- Oncetheoperationsarenished,openthegastapandignitetheboiler.
At this point it is possible to carry out any heat request.
2.9 Draining the heating system
Beforedraining,settheboilertoOFFandshuto󰀨theelectricalsupplysetting
thesystem’smainswitchto“o󰀨”
.
- Close the heating system’s taps (if present
).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beretta Ciao 25C and is the answer not in the manual?

Beretta Ciao 25C Specifications

General IconGeneral
BrandBeretta
ModelCiao 25C
CategoryBoiler
LanguageEnglish

Related product manuals