EasyManuals Logo

Beretta IDRABAGNO Lx 13 User Manual

Beretta IDRABAGNO Lx 13
Go to English
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
41
ENGLISH
7 TROUBLESHOOTING
Theapplianceshouldbeinspectedbyaqualiedprofessionalatleastonceayeartoensureitisoperatingcorrectly,prolongitslifeandmakesure
safety is optimised. This would normally involve:
- removing any rust on the burners
- removing any build-up on the electrode
- cleaning the combustion chamber
- checking that the appliance switches on and off and operates correctly
- checking the fan is operating correctly
- checking the air pressure switch
- checkingtheuegasexhaustandairintakepipes.
b
Thefollowinginstructionsareaddressedsolelytoqualiedtechniciansauthorisedtoworkontheappliance.
FAULT CAUSE SOLUTION
Boiler does not switch on
- No electrical supply - Connect to the mains
- No gas feeding - Turn the gas on
- Air in gas line - Bleed the circuit
No spark but fan operating
- Pressure switch fault - Replace
- Pressure switch tube not connected or cut - Check – replace – insert
- Ignition/amedetectionelectrodebroken - Replace
- Electrode cable cut off - Check–x
- Circuitboarddoesnotdetectame - Check–x
- Main solenoid valve does not open - Check–x
Burner does not come on
- Ignition/amedetectionelectrodebroken - Check – replace
- Electrode cable cut off - Check – replace
- Circuitboarddoesnotdetectame
- Check connector contacts and if necessary
replace the board
- Main solenoid valve does not open - Check and replace if necessary
Burner does not switch off when water shut off
- For LPG models, check the gas supply pres
-
sure
-
Adjustandifnecessaryreplacethecylinder
pressureadjuster
- Flow switch fault - Replace
Repeatedringattempts
- Specicinlet/suctionlinepipesnotinserted
correctly
- Check and repair
Burnerameinconsistentandappliancethen
switches off
- Inlet/suction line pipe not installed correctly - Check pipe seal

Table of Contents

Other manuals for Beretta IDRABAGNO Lx 13

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beretta IDRABAGNO Lx 13 and is the answer not in the manual?

Beretta IDRABAGNO Lx 13 Specifications

General IconGeneral
BrandBeretta
ModelIDRABAGNO Lx 13
CategoryBoiler
LanguageEnglish

Related product manuals