32
Table 5-2 Buzzer definition
UPS condition
Buzzer status
Fault active
Continuous
Warning active
Beep every second
Battery output
Beep every 4 seconds, if battery low, buzzer Beep
every second
Bypass output
Beep every 2 minutes
The UPS provides useful information about the UPS itself, load status,
events, measurements, identification, and settings through the front
panel display.
After powering on, the LCD will display Welcome logo for several
seconds and then enter to the default page which shows the UPS status
summary. The display automatically returns to the default UPS status
summary screen when no button has been pressed within 15 minutes.
On the UPS status summary screen it provides the following information:
Status summary, including mode and load
Alarm status, if any are present
Notes: alarm including fault and warning information
Battery and charger status, including battery voltage, charge level
and charger status
Running information and running time