UPS2 turn to fault mode
Parallel cable loss
Alarm Code: E2
In parallel systemparallel
cable disconnect
Disconnect parallel cable
one turn to fault mode
Parallel system
battery status
Alarm Code: E6
UPS1 connect battery
UPS2 without battery
Check battery connect status
Line input different
Alarm Code: E7
Parallel systemUPS1
line okUPS2 line loss
Check the line input
Bypass input
different
Alarm Code: E8
Parallel systemUPS1
bypass okUPS2 Bypass
loss
Bypass differentnot allow
turn on UPS. Check bypass
input
Power strategy
different
Alarm Code: E9
Parallel systemUPS OP
modenormal
converterHE different
Check UPS OP mode, Keep
OP mode be the same
Rate power different
Alarm Code: EA
Parallel system rate
power different
Rate power differentnot
allow turn on UPS. Keep rate
power be the same
HE in parallel
Alarm Code: EB
Parallel systemOP mode
set as HE
HE not allow in parallel
systemchange OP mode