System components
Systemlösung – 6 720 885 509 (2018/03)
12
• For information and instructions regarding the
requirements for the boiler installation room
Æ Technical information TI024
(Æ chapter 4.2, page 41)
• Equipment and complete dimensions according to
project-specific technical datasheet
• Measure the maximum weight at the front and back
feet of the foundation.
• Dimensions given with r1 % tolerance
• These dimensions are designed for standard
insulation
– 150 mm thick on floors
– 100 mm thick on casing
• The boiler types UL-S 1250/2000/2600/3200 have
inspection apertures on the right side, instead of the
bottom.
• For boiler types UL-S 1250 ... UL-S 3200, the outlet
shut-off valve and the mud quick action stop valve are
mounted in the boiler axis to the back to ensure
accessibility of the inspection aperture on the
water side.
• The boiler type UL-S 4000 has additional inspection
apertures on the side at the bottom.
• Sizing for the entrance
– Transport height: additional clearance of at least
100 mm from dimension H1 or dimension H2
(valves fitted/not fitted)
– Minimum door clearance: additional clearance of at
least 200 mm from dimension B1 or dimension B2
(valves fitted/not fitted)
• The height of the boiler room is determined by the
system equipment. The clearance above the
maintenance platform should be at least 2 m.
• For boiler types UL-S 1250 ... UL-S 3200 optionally a
shaft extension is available for the steam shut-off
valve.
• Level measurement transformer and level limiter
(image 4, [20] and [21], page 10) are positioned for
boiler type UL-S 1250 and UL-S 2000 on the top of the
boiler.
Unit UL-S
10000
UL-S
12000
UL-S
13000
UL-S
14000
UL-S
16000
UL-S
17000
UL-S
18000
UL-S
22000
UL-S
28000
Dimensions
L1
1)
1) The dimension L1 is a recommended dimension and is subject to the burner manufacturer, type and the actual steam output.
mm 8369 9007 9008 8674 9854 9920 9944 9610 9868
L2
2)3)
2) Minimum transport dimensions when valves, burner and terminal box have been removed
(without cable conduit; with cable conduit + 75 mm on the right).
3) Dimension increases depending on dimension of flue of CHP.
mm 6860 7265 7446 7456 8286 8286 8286 8705 8955
L3 mm 5550 5800 5800 5800 6630 6630 6630 7050 7050
L6 mm 980 1135 1136 1146 1146 1146 1146 1145 1395
B1 mm 3074 3224 3474 3474 3474 3669 3674 3874 4199
B2
2)
mm 2800 2950 3200 3200 3200 3400 3400 3600 4000
H1
4)
4) The dimension H1 varies depending on the valve manufacturer.
mm 3732 3867 4222 4222 4222 4467 4467 4747 5212
H2
2)5)6)
5) Dimension depending on selected flue gas temperature (influenced by number of tubes in height of economiser).
6) For boiler type UL-S 28000 there are 2 desalination connections.
mm 3065 3200 3465 3465 3465 3710 3685 3835 4302
Flue gas connection
L11 mm 503 588 588 598 598 598 598 598 778
B4 mm 240 240 380 380 380 380 380 635 600
H3
5)
mm 2923 2990 3270 3270 3270 3415 3415 3420 3585
Base frame
L4 mm 4450 4450 4700 4700 5500 5500 5500 5800 5800
L5 mm 3950 3950 4200 4200 5000 5000 5000 5200 5200
L7 mm 800 800 775 800 800 800 800 925 925
L8 mm 550 550 525 550 550 550 550 625 625
L9 mm 250 250 250 250 250 250 250 300 300
L10 mm 275 275 275 275 275 325 325 325 325
B3 mm 2080 2180 2340 2340 2340 2365 2365 2500 2700
H4 mm 140 125 140 140 140 185 185 160 225
Wide-flange beam
IPB/HEB – DIN1025 mm 200 200 240 240 240 260 260 260 300
Table 5 Dimensions and connections UNIVERSAL steam boiler UL-S 10000 ... UL-S 28000