4Settings
4.1 Standard functions
The levels and parameters displayed depend on the modules installed
and the presettings. The parameters that are not required for the
selected function are not displayed.
Parameters that are not active are highlighted in grey.
The functions of the most frequently used modules FM-MM, FM-MW and
FM-SI are described, in addition to the standard functions of the control
unit.
How to operate and call the menus via the user interface is described in
chapter 3 from page 6.
In the following tables the factory settings are highlighted in bold in the
"Settings/Adjustment range" column.
Table 3 Standard functions
Standard function Adjust Explanation/Function Remark
Date, Time Change the date and the time The date and time functions are secured via a
battery. ( Chapter 3.8, page 14)
Operating mode Auto (automatic mode) The functions behind the stored parameters
and time programs are controlled by the
control in the Operating mode "Auto".
Central heating is provided or the room
temperature is set back at the specified
times.
The operating modes can be adjusted for each
function (heat source, DHW and heating
circuit) separately. The available operating
modes vary, depending on the function.
The corresponding system components can
be called up in the "Heating mode" and
"Setback mode" operating modes but not
adjusted. The function operates with the
values stored.
Inactive fields are highlighted in grey and
cannot be changed ( Chapter 5.1.1,
page 18).
Heating mode The flow temperature is adjusted in the
Operating mode "Heating mode" so that the
higher room temperature set in the time
program (day temperature) is reached.
Setback mode The flow temperature is adjusted in the
Operating mode "Setback mode" so that the
lower room temperature set in the time
program (reduced temperature) is reached.
Manual operation Heating mode is possible, irrespective of the
times set for Auto Mode.
When "Manual operation" is selected,
automatic functions are switched off
( Chapter 5.1.1 , page 18).
Off All functions are switched off in the Off
Operating mode.
The corresponding system components can
be called up in the Off operating mode, but not
adjusted. The function is switched off.
Setting the time program for
heating circuits
Adjustment of:
•Indoor temperature
Heating times/setback mode
Modifying the standard program
Shifting switching points
Connecting switching points
Inserting set points
Deleting switching points
Linking heating phases
Deleting heating phases
Creating new time program
If the system has several heating circuits, the
settings for each heating circuit must be made
separately.
( Chapter 5.2, page 18)
( Chapter 6.2, page 22)
Setting the DHW time
program
Adjustment of:
Water temperature
Heating times/setback mode
Modifying the standard program
Shifting switching points
Connecting switching points
Inserting set points
Deleting switching points
Linking heating phases
Deleting heating phases
•DHW heating
Creating a new DHW program
Creating a new circulation program
To prevent legionella bacteria from
multiplying in the DHW, the DHW (including
solar cylinder, if installed) is heated to 60 °C
once a day.
If the system has several DHW circuits, the
settings for each DHW circuit must be made
separately.
( Chapter 4.3, page 17)
( Chapter 6.2.4, page 24)