Operating and fault displays
Control 8311/8313 – 6720859790 (2020/02)
28
Table 7 Unit troubleshooting
DHW remains cold Heating of DHW is stopped. Current
DHW temperature is below 40 °C.
The set DHW temperature is set
incorrectly.
Adjust the set DHW temperature.
The time program has been set
incorrectly.
Reprogram the
time program.
The DHW temperature is not rising. Check whether the DHW circuit is
in automatic mode.
▶Phone Service.
Thermal disinfection failed Thermal disinfection has been
aborted.
The output of the heat source is
insufficient, e.g. because other
heat consumers (e.g. heating
circuits) demand heat during
thermal disinfection.
The temperature sensor is
incorrectly connected or faulty.
The cylinder primary pump is
incorrectly connected or faulty.
FM-MW module or control unit is
faulty.
The draw-off quantity during
thermal disinfection is too high.
Select the time for thermal
disinfection so that there is no
overlap with additional heat
demands.
▶Phone Service.
Manual operation activated Boiler is operating in accordance with
the specifications in manual operation
Chapter 3.7.3, page 13.
Manual operation activated Deactivate manual operation
Chapter 3.7.3, page 13.
Flue gas test is active Control operates for max. 30 minutes
with higher flow temperature
Chapter 3.7.2, page 12.
Flue gas test is active Deactivate flue gas test
Chapter 3.7.2, page 12.
Position test for temp. limiter
sensor activated
The boiler heats until the high limit
safety cut-out is triggered.
High limit safety cut-out position
test was carried out.
Release the key and
key.
Reset control with
Chapter 3.7.1, page 12.
Manual operation pump... A manual mode was activated. Deactivate manual operation.
...Temperature sensor
defective
Depending on the faulty sensor. Phone Service.
No voltage behind the internal
safeguard for ZM5311 burner
output
Burner is not going into operation. Internal safety device of burner has
triggered.
Current consumption by the
burner is too high.
▶Phone Service.
Display text/Observation/
Fault
Effect on the control characteristics Cause Remedy
reset