Notification Appliance Circuit Module Wiring | en 13
Bosch Security Systems, Inc. Installation manual 2020.05 | 04 | 4998122260
5.2 Wiring the module with BSeries control panels
5.2.1 Wiring interconnected loops with 12VDC power supplied by the panel
This wiring scheme allows up to 12 D192G modules (NAC loops) triggered by a single
programmed alarm output.
Figure5.5: Wiring interconnected modules to a BSeries panel supplying 12 VDC power
1 Last D192G module on the
interconnected NAC loop
8 Positive (+) connection between
panel’s aux power and module’s aux
and ext power terminals
2 Polarized notification devices 9 Connection to module’s ALRM TRG
terminal
3 560Ω, 2W EOL resistors (P/
N:F01U008725)
10 Connection between module’s SUPV
ZONE and panel zone
4 First D192G module on the
interconnected NAC loop
11 Connection to panel’s Aux power
(+12V)
5 BSeries control panel 12 Connection between module COM and
panel’s digital COM (not to earth
ground)
6 Connection to either B or C
programmed output
13 1kΩ EOL resistor (P/N:F01U011298)
7 D134 Dual Relay Module (as example)