18 en | Programming Notification Appliance Circuit Module
2020.05 | 04 | 4998122260 Installation manual Bosch Security Systems, Inc.
6 Programming
6.1 Supervisory zone
Several options are available to program the module’s supervision point. Program the point
using a point index configured as:
Point Type 0 (24 h)
Pt Response 9
– Short = Fire Supervision;
– Open = Fire Trouble
Buzz on Fault = 2
Fire = Yes
Program all other selections for the point index number No.
6.2 Alarm output
For instructions on programming the control panel, refer to the panel's Program Entry Guide.
For compatibility information about synchronization modules and strobes, refer to the panel's
Approved Applications Compliance Guide.