Notification Appliance Circuit Module Wiring | en 9
Bosch Security Systems, Inc. Installation manual 2020.05 | 04 | 4998122260
5.1 Wiring the module with GSeries control panels
5.1.1 Wiring interconnected loops with 12VDC power supplied by the panel
This wiring scheme allows up to 12 D192G modules (NAC loops) triggered by a single
programmed alarm output.
Figure5.1: Wiring interconnected modules to a GSeries panel supplying 12VDC power
1 Last D192G module on the
interconnected NAC loop
6 1kΩ EOL resistor (P/N:F01U011298)
2 Polarized notification devices 7 Connection to either Relay A or Relay
B programmed output
3 560Ω, 2W EOL resistors (P/
N:F01U008725)
8 Connection between module SUPV
ZONE and panel zone
4 First D192G module on the
interconnected NAC loop
9 Connection between module COM and
panel’s COMMON (not to earth
ground)
5 GSeries control panel 10 Positive (+) connection from panel’s
AUX POWER and module’s AUX PWR IN
and EXT PWR IN terminals