EasyManua.ls Logo

Bosch D7412GV3 - D7212 GV3 Power Supply Side Wiring Diagram

Bosch D7412GV3
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 en | Diagrams Control Panels
F.01U.167.105 | 02 | 2010.11 UL Installation Instructions Bosch Security Systems, Inc.
2.2.2 D7212GV3 Power Supply Side Wiring Diagram
Callout Description Callout Description
1 If required by local AHJ, connect D113
Battery Lead Supervision Module.
8 D192G Bell Supervision Module
2 Batteries 9 To Relay A or Relay B
3 D122 Dual Battery Harness, as required 10 Listed Audible Signaling Devices rated at 12.0
VDC nominal (Do not use vibrating type horns.)
4 D1640 Transformer and D8004 Transformer
Enclosure required for NFPA Applications
11 C900V2 (optional)
5 D8132 Dual Battery Charger with two
batteries (Batteries are not supervised.)
12 560 Ω, 2 W EOL Resistor (P/N: 15-03130-005)
6 Power limited, supervised 13 RJ31X, primary telephone line
7 Power limited 14 To earth ground
NOTICE!
All external connections except Terminal 5 (battery positive) are power limited.