EasyManua.ls Logo

Bosch D7412GV3 - Input Points and Peripheral Devices Wiring Diagram (D9412 GV3 Shown)

Bosch D7412GV3
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Panels Diagrams | en 11
Bosch Security Systems, Inc. UL Installation Instructions F.01U.167.105 | 02 | 2010.11
2.3 Input Points and Peripheral Devices Wiring Diagram
(D9412GV3 shown)
Callout Description
1 (Optional): For 24 V applications use a UL 1481 Listed regulated, power-limited 24 VDC power supply
with a D130 Relay Module. Refer to the D130 Installation Instructions (P/N: F01U072455) for correct
wiring requirements.
2 D130 Relay Module
3 D125B Powered Loop Interface Module
4 To UL Listed two-wire smoke detectors. Refer to Two-Wire Smoke Detectors in the D9412GV3/D7412GV3
Approved Applications Compliance Guide (P/N: F01U143069) for a listing of compatible two-wire smoke
detectors.
5 P105BL1 1 kΩ EOL resistor (P/N: F01U033966): For typical burglar alarm applications.
6 D129 Dual Class A Initiation Circuit Module: Provides optional Waterflow Alarm Retard feature. Not
suitable for two-wire smoke detectors.
NOTICE!
Use zero retard except for waterflow devices.
All external connections except Terminal 5 (battery positive) are power limited.