EasyManua.ls Logo

Bosch D7412GV3 - D7412 GV3 SDI Devices Wiring Diagram

Bosch D7412GV3
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control Panels Diagrams | en 13
Bosch Security Systems, Inc. UL Installation Instructions F.01U.167.105 | 02 | 2010.11
2.4.2 D7412GV3 SDI Devices Wiring Diagram
Callout Description
1
Up to 16 supervised keypads or fire annunciators
1
2 Up to 2 D9210B Access Control Interface Modules
3 Up to 1 supervised 9131A Parallel Printer Interface Module, or other SDI device
4 Power limited, supervised
5 DX4020 Network Interface Module or other SDI device
6 Power limited
7 D8125 POPEX No. 1
8 Up to 67 D9127U/T POPITs
9
Zonex 1: Up to 9 D8128Ds maximum
2
10
Zonex 1: Up to 8 D8129s maximum
2
1
D1255 (all models), D1255RB, D1256, D1256RB Keypads, or D1257RB or D1257 Fire Annunciators, or up to 8 D1260 Keypads (all
models).
2
The number of D8129 OctoRelays that can be connected to each zonex terminal on the control panel is limited by the number of
D8128D OctoPOPITs connected to the same terminal. Refer to the D8128D Installation Guide (P/N: F01U070537) or the D8129
Operation and Installation Guide (P/N: F01U036302) for specific information.
NOTICE!
All external connections except Terminal 5 (battery position) are power limited.
Fire and Intrusion devices must be on separate circuits. Refer to ICP-SDI-9114 Installation
Instructions (P/N: F01U030068).