Page 128 P/N: 4998152533-02 Copyright 2007 Bosch Security Systems, Inc. DS7200V2-UK Installer's Guide
PART V: REFRENCE MATERIALS
Event #
Event as shown
in Panel Log
SIA Report
SIA Report Data
Contact ID Report
Event Description
Zone Types
Linked to
Event
RPS
Event
Group
Status
Reports
76 Fire,Cross Fire Alarm
Cross Zone
ri {area} FM {loop} 110 Fire Verified alarm event on fire
zone type with Cross Zone
Option. See Zone
Response Options on page
81.
1- Fire
2
77 Fire,Un-verified Unverified
Event-Fire
ri {area} FG {loop} 378 Cross-zone
Trouble
Unverified alarm event on
fire zone type with Cross
Zone Option. Or unverified
event on Fire Verify zone
type..
1- Fire
2- Fire with
Alarm
Verification
5
78 Fire, Missing Missing Fire
Trouble
ri {area} FY {loop} 373 Fire Trouble Fire zone type assigned to
zone expander (wired or
RF) not responding to
panel’s status poll.
1- Fire
2- Fire with
Alarm
Verification
5
79 Fire,Alrm,Rstl Fire Alarm
Restore
ri {area} FH {loop} 110 Fire Restoral from alarm, Fire
zone types
1- Fire
2- Fire with
Alarm
Verification
7
80 Fire, Fault Fire Trouble ri {area} FT {loop} 373 Fire Trouble Fault (Trouble) condition on
Fire zone types
1- Fire
2- Fire with
Alarm
Verification
5
81 Fire,Trbl,Rstl Fire Trouble
Restore
ri {area} FJ {loop} 373 Fire Trouble Restoral from Trouble, Fire
zone types.
1- Fire
2- Fire with
Alarm
Verification
7
82 Instl Mode,Start Local Program LB 466 Service On
Premises
Installer PIN entered.
Installer mode accessed.
11 R
83 Instl Mode,End Local
Programming
Ended
LX 466 Service Off
Premises
Installer mode exited. 11 R
84 Log Overflow Log Overflow JO 624 Event Log
Overflow
Panel log overflow
condition. Oldest events
being overwritten.
12 R
85 Log Threshold Log Threshold JL 623 Event Log Panel log reached
threshold. See Log
Supervision Configuration
on page 50.
12 R
86 AltCom Low Signl Low Received
Signal Strength
XL {device address}
350
Communication
Trouble
Low Signal Strength
detected on Alternate
Communication device.
12 R S
87 Missing,Alarm Untyped
Missing Alarm
ri {area} UZ {loop} 150 General Alarm
Zone assigned to zone
expander (wired or RF) not
responding to panel’s status
poll while system is armed.
8
10 - 15
3
88 Missing, Fault Untyped
Missing
Trouble
ri {area} UY {loop} 382 Loss of
supervision
Zone assigned to zone
expander (wired or RF) not
responding to panel’s status
poll while system is
disarmed.
3 - 8
10 - 15
6
89 Open,Tmr Automatic
Opening
ai {252} OA {area} 403 Automatic O/C
Opening by Sked (Timer). 10
90 Open, RPS Remote
Opening
ri {area} OQ {254} 400 Open/Close Opening by RPS.
91 Open,Usr Opening
Report
ri {area} OP {user} 401 O/C by User Opening by user, by ID
reported.
10
92 Open,KS Opening
Keyswitch
ss {255} OS {area} 409 Keyswitch O/C
Opening by Keyswitch. 10
93 Open,Tmr,Alarm Disarm from
Alarm
ri {area} OR {252} 403 Automatic O/C
Opening after Alarm event
by Sked (Timer).
10
Table 47: Control Panel Events and Reporting Formats (continued)