Mini VRF Heat Pump Outdoor Unit 6 720 874 421 (2017/04) ZA
INSTALLING THE CONNECTIVE PIPEWORK | 7
4.6 Illustration
N1
(28)
N
3
(28)
N
5
(28)
N
6
(22)
N
2
(28)
N
4
(28)
A
B
D
E
C
a
b
c
e
f
d
L
1
L2
L5
L3
L4
Outdoor Unit((Take Model 160 For Example)
The First Branch Pipe
Indoor units
Fig. 4-6
Caution: Ensure both liquid and gas pipework combined does not exceed
90m.
Indoor unit branch pipe
Inner branch pipes are a~f, for size selection please refer to Table4-6.
Note: The Maximum length of the branch pipe should not exceed
more than 15m.
The main pipes for the indoor units and the indoor unit branch pipe
components.
The downstream inner units of the main pipe L2 are N1,
N2, and its total capacity is 28×2=56, the size of pipe
L2 is Ø15.9/Ø9.5, and the branch pipe B should be
IDU - 01.
The downstream inner units of the main pipe L4 are N3,
N4, and its total capacity is 28×2=56, the size of pipe
L4 is Ø15.9/Ø9.5, and the branch pipe D should be
IDU - 01.
The downstream inner units of the main pipe L5 are N5,
N6, and its total capacity is 28+22=50, the size of pipe
L5 is Ø15.9/Ø9.5, and the branch pipe E should be
IDU - 01.
Allowable length and height difference of refrigerant pipes
Table 4-11
Permitted value Pipework
Pipe Length
Total Pipe Length (Actual) ≤100 m L1+L2+L3+L4+L5+a+b+c+d+e+f
Maximum Pipework (L)
Actual Length
≤45 m (8 kW, 10.5 kW)
≤60 m (12 kW, 14 kW, 16 kW, 18kW)
L1+L2+L3+L4+L5+f
(The first connection method)
Equivalent Length
≤50 m (8 kW, 10.5 kW)
≤70 m (12 kW, 14 kW, 16 kW, 18kW)
or L1+L3+L5+f
(The second connection method)
Pipe Length (from the first line branch pipe
to furthest indoor unit)(m)
≤20 m L2+L3+L4+L5+f (The first connection method)
or L3+L5+f (The second connection method)
Pipe Length (from the nearest branch pipe
equivalent length(m)
≤15 m
a, b, c, d, e
Drop Height
Indoor Unit-Outdoor
Unit Drop Height (H)
Outdoor Unit up
≤30 m
______________
Outdoor Unit Down
≤20 m
______________
Indoor Unit to Indoor Unit Drop Heihgt (H)
≤8 m
______________
Note: When the distance of the refrigerant pipework is over 90m, the system will decrease in capacity. You must increase the gas pipe by one size.
The first connection method
Indoor Unit
The First Line Branch Pipe
Outdoor unit
a
A
L2
L1
B
C
D
E
L3 L4 L5
b
c
d
e f
Pipe length(From the nearest branch pipe equivalent length)
Maximum pipe equivalent length
(From the first line branch pipe) Maximum pipe equivalent length
Fig. 4-7