26 en | Troubleshooting
Professional Series TriTech AM Motion Detectors
with Anti-mask, LSN
2018.10 | 01 | F.01U.352.414 Reference Manual Bosch Building Technologies
9 Troubleshooting
9.1 Detector does not appear to respond to motion
Potential causes
Insufficient power
Loose wires in the terminals
Cabling or wiring error
Defective unit
Walk test LED is disabled
Detector is not level vertically or horizontally
Notice!
Some regulations require that you disable the LED after the walk test.
9.2 Detector is in continuous alarm
Potential causes
Mounting location does not meet the recommendations listed in this document
Insufficient power
Input loop continuity broken
Incorrect alarm loop resistance configuration
Defective unit
Masking attempt detected
9.3 Detector appears normal but does not send alarms to the
control panel
Potential causes
Incorrect alarm loop resistance configuration
Incorrect alarm loop wiring
9.4 Detector does not appear to detect motion in the space
directly under it
Potential causes
The look-down zone is disabled
9.5 Detector does not appear to detect motion in farthest coverage
area
Potential causes
Microwave range is too short
Verify that the correct detection range is selected in RPS
9.6 Detector LED flashes continuously
Potential causes
Warm-up mode requires a certain amount of time with no motion in the area to settle the
PIR and microwave circuit
Defective unit
Detector indicates an alarm event stored in the memory during the last Armed (Set) mode

Related product manuals