Battery Charger Technical Data | en 33
Bosch Security Systems B.V. Installation and Operation manual 180110011Aa | V1.1 | 2011.05
11.2 Mechanical
11.3 Environmental conditions
11.4 Approvals and compliance with standards
This product is compliant with LV and EMC directives (immunity and emission).
11.4.1 Safety approvals
C-Tick (Australia)
–CE (Europe)
11.4.2 EMC approvals
EN50130-4: 1995 +A1: 1998, A2:2003 Alarm systems (Immunity requirements for
components of fire, intruder and social alarm systems).
EN60950-1 (2006), EN61000-6-1 (2007), EN61000-6-2 (2006), EN61000-6-3 (2007),
EN61000-6-4 (2007), and EN 55022 class B (2007).
11.4.3 Voice Alarm System related approvals
EN54-4: 1997 and amendment A2 (February 2006): Fire detection and fire alarm systems
(Part 4: Power supply equipment).
CE CPD Numbers are: 0333-CPD-075381-1 (PLN-24CH12) and
0333-CPD-075383-1 (PRS-48CH12). They have been affixed in 2011.
EN 12101-10 class A (January 2006): Smoke and heat control systems. Part 10: power
supplies.
Dimensions (h x w x d) 44.5 x 483 x 310 mm (19” wide, 2RU high)
Weight approx. 6 kg
Operating temperature range
-5 to +45
o
C
Storage temperature range
-25 to +85
o
C
Altitude Under 76 kPa, the max operating temperature
decreases of 5°C every 10 kPa.
Cooling operates transversely.
Relative humidity (Operating and non
Operating)
20 - 95% without condensation
Make sure that the battery charger is not exposed
to sources of water or to water splashes.