EasyManua.ls Logo

Bosch PRS-48CH12 - Product View; Front Panel Indicators

Bosch PRS-48CH12
35 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Battery Charger System Overview | en 9
Bosch Security Systems B.V. Installation and Operation manual 180110011Aa | V1.1 | 2011.05
3.4 Product view
3.4.1 Indicators on the front panel
Figure 3.1 Front view of battery charger
Fault signalling occurs with three LEDs at the front side as well as three fail-safe outputs on
the rear panel for remote monitoring (refer to section 3.4.2 ).
Status LED Green Yellow
A Mains status OK - Mains voltage threshold <165 Vac ±5% (Auto
reconnect at >185 Vac ±5%).
- Primary fuse (F1) is blown.
- Power supply is broken.
- Internal battery charger temperature is too high
(>65°C).
B Battery status OK - The battery is not present.
- The internal impedance (Ri) is too high
(see section 5.1 and 8.1.1 ).
- When the mains is present and the battery voltage
during normal use is:
PLN-24CH12: <23.5 Vdc ±3%
PRS-48CH12: <47,0 Vdc ±3%
- When the mains is present and the battery voltage
during start-up is:
PLN-24CH12: Vbat ≤ 14 Vdc, Vbat ≥ 30 Vdc (±3%)
PRS-48CH12: Vbat ≤ 40 Vdc, Vbat ≥ 60 Vdc (±3%)
- When battery is connected in reverse when
commisioning the system
C Output voltage status OK - No voltage on one or more output.
- Fuse (F8) broken.