Product information 43/128
CytroBox, RE 51057-B/11.19, Bosch Rexroth AG
Table 37: Warnings
Description of diagnosis
S-0-0390 P-0-1300 S-0-0095 Cause Remedy
E2013 B300 B300: oil level of tank
very high
The monitoring of the oil level
indicates a warning.
P-0-1291 > P-0-1389[72]
Check/reduce the oil volume in the tank.
Check the limit value.
Check the sensor output signal.
E2013 B301 B301: oil level of tank
very low
The monitoring of the oil level
indicates a warning.
P-0-1291 < P-0-1389[71]
Check/increase the oil volume in the tank.
Check the limit value.
Check the sensor output signal.
E2013 B302 B302: particle content S
very high
The monitoring of the particle
concentration indicates a
warning.
P-0-1424 > P-0-1389[61]
Check the limit value.
Check the sensor output signal.
Change the oil.
E2013 B303 B303: particle content
M very high
The monitoring of the particle
concentration indicates a
warning.
P-0-1425 > P-0-1389[62]
Check the limit value.
Check the sensor output signal.
Change the oil.
E2013 B304 B304: particle content L
very high
The monitoring of the particle
concentration indicates a
warning.
P-0-1426 > P-0-1389[63]
Check the limit value.
Check the sensor output signal.
Change the oil.
E2013 B305 B305: particle content
XL very high
The monitoring of the particle
concentration indicates a
warning.
P-0-1427 > P-0-1389[64]
Check the limit value.
Check the sensor output signal.
Change the oil.
E2013 B306 B306: filter clogging
very high
The monitoring of the filter
contamination indicates a
warning.
(P-0-1273 – S-0-0813)
> P-0-1389[30]
Check the limit value.
Check the sensor output signal.
Replace the filter element of the pressure
filter.
E2013 B307 B307: oil temperature
very high
The monitoring of the oil
temperature indicates a warning.
P-0-1280 > P-0-1389[26]
Check the limit value.
Check the sensor output signal.
Reduce the current load.
Check the oil cooling pump.
Check the water cooling unit.
E2013 B308 B308: oil temperature
very low
The monitoring of the oil
temperature indicates a warning.
P-0-1280 < P-0-1389[25]
Check the limit value.
Check the sensor output signal.
Heat the oil.
E2013 B309 B309: oxygen content
very high
The monitoring of the air
inclusion indicates a warning.
P-0-1270 > P-0-1389[7]
Check the limit value.
Check the sensor output signal.
Check the degassing function.
Reduce the required flow.
E2013 B310 B310: relative humidity
very high
The monitoring of the relative
humidity indicates a warning.
P-0-1272 > P-0-1389[13]
Check the limit value.
Check the sensor output signal.
Check the drainage function.
Reduce the required flow.
E2013 B314 B314: system pressure
very low
The degassing function should
run (P-0-1270 > P-0-1389[2]) but
the oil system pressure is too
low (S-0-0813 < P-0-1389[3]).
Check the limit values.
Perform a pressure control with a higher
command value.
Check the sensor output signal.