RE 30232-02-B, Edition 02.2021, Bosch Rexroth AG
Mounting | Valve amplifier VT-MSPA2-2X 17/36
Table 7: Recommended cable variants
Table 8: Clamping range, rated connection
Min. Max.
Rigid 0.2 mm² 2.5 mm²
Flexible 0.2 mm² 2.5 mm²
Flexible with wire end ferrule 0.25 mm² 2.5 mm²
The length to be stripped is 10 mm each.
7.5.3 Connecting the individual contacts
Fig. 3: XG20/XG21: “PUSH-IN“ contact
Interface Maximum
length [m]
Cable type Minimum
cross-section
[mm
2
]
Remarks
Digital in/out
30 Unshielded 0.25 to 2.5 For 30 m or more, shielded cable
required
50 Shielded 0.25 to 2.5
Command
value
30 Twisted pair 0.25 to 2.5 For 30 m or more, shielded cable
required
50 Twisted pair, shielded 0.25 to 2.5
Actual value
30 Twisted pair 0.25 to 2.5 For 30 m or more, shielded cable
required
50 Twisted pair, shielded 0.25 to 2.5
Solenoid cable
20 Unshielded 1.0 to 1.5
50 Unshielded 1.5 to 2.5
Operating
voltage
20 Unshielded 1.0 to 1.5
50 Unshielded 1.5 to 2.5
Solid wire
With wire end ferrule
Flexible wire
1.
2.
3.