Operation 33/46
RE51550-B/09.2019, BoschRexrothAG
5.2 WGM-B
This operation explanation refers to sensor options without display units
5.2.1 Switch-on procedure
When the device is connected to the supply voltage, it switches on immediately.
With IO-Link, the sensor is in SIO mode if the master is not present. In SIO mode,
the sensor operates like a normal PNP switching output.
5.2.2 Parameter settings
The parameters can be set as switching point, switch-back point or temperature unit
via the IO-Link interface.
5.2.3 Factory setting
(can only be restored via IO-Link)
Switching outputs Basic settings
Switching point
switch-back point
80% / 75% Error message Inactive
Delay switching point/
switch-back point
0 / 0 Temperature unit °C
Characteristic Hysteresis as
normally closed
contact (Hnc)
Assignment switching
output
Humidity
5.2.4 Switching outputs
The sensor is equipped with a switching output which is assigned to the humidity.
The threshold value is pre-set to 80%. The switching function is designed as a
normally open contact. This switching output can be configured ex works or via the
digital interface.
For information on the functionality, please refer to chapter Switching outputs
[> page22].
5.2.5 Analog outputs
The sensor version is equipped with up to two 4-20mA analog outputs. The analog
outputs are available for relative humidity and temperature. The scaling is pre-set
and can be configured ex works or via the digital interface. By default, the relative
humidity is represented at the analog output from 0% to 100%. The temperature is
represented at the analog output from -20°C to 120°C.