EasyManua.ls Logo

Bosch Rexroth WGM - 9.4 Outputs WGM-B; WGM-B Output Configurations (2 A1 S, 1 D0 S); 9.5 Outputs WGM-R; WGM-D; WGM-R;WGM-D Output Configurations (2 A2 S, 1 D1 S)

Bosch Rexroth WGM
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix 39/46
RE51550-B/09.2019, BoschRexrothAG
Analog output Selectable current or voltage output
(4 - 20mA, 2 - 10V, 0 - 10V or 0 - 5V)
Tolerance ± 0.5% FS
Load Ω = (U
B
- 8V) / 0.02A
Switching output
PNP switching output Selectable switching function and switching output
Switching current max.0.2A per output
Temperature
measurement
Measurement range -20°C to +120°C
Accuracy ± 1.5% FS
Analog output Selectable current or voltage output
(4 - 20mA, 2 - 10V, 0 - 10V or 0 - 5V)
Tolerance ± 0.5% FS
Load Ω = (U
B
- 8V) / 0.02A
9.4 Outputs WGM-B
Version 2A1S 1D0S
Connector (base) 1xM12 – 8-pin 1xM12 – 4-pin
Switching output
(fixedly set)
X
IO-Link X
Analog output for
humidity
X
Analog output for
temperature
X
9.5 Outputs WGM-R / WGM-D
Version 2A2S 1D1S
Connector (base)
Display & remote
1xM12 – 8-pin 1xM12 – 4-pin
Sensor connection
socket (bottom) remote
1xM12 – 8-pin 1xM12 – 8-pin
Switching outputs 2 x 1 x
IO-Link X
Analog output for
humidity
X
Analog output for
temperature
X

Table of Contents