Location 660
Siren Run Time (V1.10 – 2.03)
Location 660
Siren Run Time
(V2.04+)
Location 661
Siren Sound Rate
Location 662
Swinger Shutdown Count
For Siren and Dialler
(V1.10 – 1.37)
Location 662
Swinger Shutdown Count
For Siren
(V1.40+)
Location 663
Dialler Options 1
Location 664
Dialler Options 2
Location 665
System Options 1
Location 666
System Options 2
Location 667
System Options 3
Location 668
System Options 4 (V1.10 Only)
Location 668
System Options 4 (V1.20+)
Location 669
Consumer Options 1 (V1.10 Only)
Location 669
Consumer Options 1 (V1.20+)
Location 670
Consumer Options 2
10
0 = No Siren Time / 1 - 15 = Siren Time In Minutes (Default = 10 Min’s)
5
0 = No Siren Time / 1 - 15 = Siren Time In Minutes (Default = 5 Min’s)
7
0 = Slowest Frequency / 15 = Fastest Frequency
0
0 = No Lockout / 1 - 15 = Number Of Times Siren/Dialler Operate Till Lockout
0
0 = No Lockout / 1 - 15 = Number Of Times Siren Operate Till Lockout
5
1 = Dialler Reporting Functions Allowed
(Disable In V2.00 Also Disable Safecom)
2 = Remote Arming Via Telephone Allowed
4 = Upload/Download Via Alarm Link Allowed
8 = Terminate Alarm Link Session On Alarm
0
1 = Open/Close Reports Only After Alarm
2 = First To Open/Last To Close Reporting (Partitioned Systems Only)
4 = Open/Close Reports In STAY Mode Allowed
8 = Answering Machine Bypass Only When Armed (V1.31 +)
1
1 = Forced Arming Allowed
2 = Smart Lockout Allowed
4 = Horn Speaker Monitor
8 = Horn Speaker Beeps Allowed
2
1 = Keyswitch Interface, Night Arm Station or RE005 Installed
2 = Handover Delay To Be Sequential
4 = Codepad Panic To Be Silent
8 = Access Denied (Code Retries/Codepad Tamper) To Be Silent
0
1 = Area 1 Codepad Connected To Main Data Terminal
2 = Modem Module Required For Alarm Link Operation
4 = AC Fail After 1 Hour (Disabled = After 2 Minutes)
8 = Pulse Count Handover Allowed
0
1 = Delay Audible Alarm Until Communication Complete
2 = Reset Alarm Outputs From Any Area (Partitioned Systems Only)
4 = Auto Arm In AWAY Mode
8 = Auto Arm In STAY Mode 1
0
1 = Delay Audible Alarm Until Communication Complete
2 = Reset Alarm Outputs From Any Area (Partitioned Systems Only)
4 = Ignore AC Mains Fail (V1.30+)
8 = Auto Arm In STAY Mode 1
2
1 = Entry Guard Time In STAY Mode
2 = Audible Alarm In STAY Mode Allowed
4 = User Code Required To Isolate Zones
8 = Codepad Extinguish Mode Allowed
2
1 = STAY LED To Display Day Alarm On/Off Status
2 = Audible Alarm In STAY Mode Allowed
4 = AUX LED To Display Dialler On-Line (Partitioned Codepad Only)
8 = Codepad Extinguish Mode Allowed
2
1 = ‘User Code + 0 + AWAY’ Function To Arm/Disarm All Areas Allowed
2 = Single Button Arming Allowed (AWAY, STAY Mode 1 & STAY Mode 2)
4 = Single Button Disarm Allowed (STAY Mode 1 or STAY Mode 2)
8 = Alarm Reset Memory On Disarm
16 Solution-16/Solution-16
Safecom
Quick Reference Guide
SOL 16 SAFECOM QUICK REF GUIDE.DOC.DOC Bosch Security Systems Pty Limited