*Pulsing Mode
When you program the output polarity as pulsing, the time base becomes the ON time and the
multiplier becomes the OFF time. The OFF time is the time base x the multiplier. (For
example, if you want the output to pulse 1 sec. ON and 5 sec. OFF, you would program time
base as 2 and the multiplier as 05.)
Notice!
When event code Remote control 1 – 20 is selected, polarity mode shall be programmed as
time-independent option (including 1 = Normally open, going low, or 7, or 8, and 14).
Time Programming
Entry Time 1
Item Location Option Default New
Increments of 1 sec. (0 to 15 sec.) 0466
4
Increments of 16 sec. (0 to 240 sec.) 0467 1
Entry Time 2
Item Location Option Default New
Increments of 1 sec. (0 to 15 sec.) 0468
8
Increments of 16 sec. (0 to 240 sec.) 0469 2
Exit Time (AWAY/STAY Modes)
Item Location Option Default New
Increments of 1 sec. (0 to 15 sec.) 0470
12
Increments of 16 sec. (0 to 240 sec.) 0471 3
Entry Guard Time For STAY Mode
Item Location Option Default New
Increments of 1 sec. (0 to 15 sec.) 0472
0
Increments of 1 6sec. (0 to 240 sec.) 0473 0
Delay Alarm Report Time
Item Location Option Default New
Increments of 1 sec. (0 to 15 sec.) 0474
0
Increments of 16 sec. (0 to 240 sec.) 0475 0