Important: bathroom locations and clearances
The boiler must not be installed in Zone 1
Any switch or appliance control using mains electricity
must not be within reach of a person using the bath
or shower
Electrical switches (other than pull cords), fused spurs
and socket outlets must not be situated in the bathroom
A boiler fi tted with a mechanical timer or RF mechanical
timer (receiver) or FW100 controller may only be installed
outside the shaded area. A boiler with any other timer
tted (or blanking panel for an optional programmer) can
be installed in zone 2.
Additional Residual Current Device (RCD) protection may
be required.
Refer to the latest IEE wiring regulations.