X20 system
3.4.1.2.1 Cable shielding via X20 shielding bracket
Attaching the shield with a ground terminal
X20AC0SF7.0010 - 66 mm shielding bracket
Attaching the shield with a ground terminal
X20AC0SF9.0010 - 88 mm shielding bracket
Cable duct
Cable duct
Table 4: Cable shielding via X20 shielding bracket
To reduce EMC emissions as much as possible, the cable shield must reach as high as possible after attaching
the cable to the shielding bracket (see in the figure above).
Notice!
A minimum spacing of 35 mm between the X20 module and shielding bracket must be observed.
Additional spacing may result from the bend radius of the cables.
Installation / EMC guide 1.36 (April 2021) 17