General requirements
Characteristics Specification
-25 to 60°C Horizontal mounting orientationX20 standard modules,
X20 coated modules,
X20 coated safety modules
-25 to 50°C Vertical mounting orientation
0 to 60°C Horizontal mounting orientationX20 safety modules
0 to 50°C Vertical mounting orientation
X67 modules -25 to 60°C Any mounting orientation
Power Panel 65 0 to 50°C Vertical and horizontal mounting orientation
Power Panel T30 -20 to 60°C Vertical and horizontal mounting orientation
Ambient temperature during operation
Power supplies -25 to 70°C Horizontal mounting orientation (>55°C derating)
X20 standard modules,
X20 safety modules,
Power supplies
Up to 95% non-condensing
X20 coated modules,
X20coated safety modules,
X67 modules
Up to 100% Condensing possible
Relative humidity during operation
Power Panels Up to 90% non-condensing
0 to 2000 m Installation at elevations above sea levelOperating elevation All products
>2000 m See data sheet.
All X20 modules 1 g Requirement in accordance with EN 61131-2
X67 modules 2 to 4 g Requirement in accordance with EN 60721-3-5 / Class 5M3
Resistance to vibration during operation
(EN 60068-2-6)
Power supplies 2.3 g Requirement in accordance with EN 61131-2 and DNV-GL /
Class C
All X20 modules,
Power Panels,
power supplies
15 g Requirement in accordance with EN 61131-2Shock resistance during operation
(EN 60068-2-27)
X67 modules 30 g Requirement in accordance with EN 60721-3-5 / Class 5M3
(Type I)
All X20 and X67 modules,
Power Panels
II Requirement in accordance with EN 61131-2Overvoltage category
(EN 60664-1)
Power supplies III Requirement in accordance with EN 60204
Pollution degree (EN 60664-1) All products 2 Requirement in accordance with EN 61131-2
All X20 modules,
Power supplies
IP20 Control cabinet installation required
X67 modules IP67 No installation required
Front: IP65
Protection rating (IP code)
(EN 60529)
Power Panels
Back: IP20
Rear-side installation required
Table 12: General requirements - Environmental characteristics
1 g = 10 m/s²
In addition to the general specifications in this table, the technical data of the respective products must be checked and any necessary derating must be taken
into account!
Vibration and shock resistance values are valid only under the condition that the connection lines are installed properly and components are mounted correctly.
Definitions in accordance with EN 60664-1
Overvoltage category II: Energy-consuming equipment supplied by the fixed installation
Overvoltage category III: Equipment in fixed installations and for cases where the reliability and the availability of the equipment is subject to special
requirements
Pollution degree 2: Only non-conductive pollution occurs. Occasionally, however, temporary conductance may result from condensation.
Protection rating provided by enclosure (IP code) in accordance with EN 60529
First number IP2x Protection against ingress of solid foreign bodies ≥12.5 mm diameterIP20 protection
Second number IPx0 No protection against ingress of water with damaging consequences.
First number IP6x Dust-proofIP65 protection
Second number IPx5 Protection against water jets
First number IP6x Dust-proofIP67 protection
Second number IPx7 Protection against temporary submersion
40 Installation / EMC guide 1.36 (April 2021)