Troubleshooting Thermostatic Mixing Valve
Problem Cause Solution
system
Either the NPT joints or the o-rings have been
damaged.
for O-Ring Seal Kit (S65-173).
The thermostat has failed and, subsequently, the
safety shut-off has engaged.
Inspect Thermostat:
1. Remove the top cap and pull out the push rod and thermostat.
1/2" ).
thermostat must be replaced (it cannot be repaired). Contact your
The inlet shut-off valve may be partially closed
pressure.
screen or seat, limiting the movement of the stop
Clean Stop and check Valves:
reassemble the valve. Do not remove the seat. The components
Temperature fluctuation
or improper Temperature
move freely.
Inlet supply line to the mixing valve is being
shared by other pieces of equipment that are
used only periodically, such as laundry appliances
pressure to the mixing valve to less than 10 PSI.
supply both the valve and the other appliances.
the supply usage.
Recirculation is not balanced.
Piston does not move freely and must be cleaned. See next page for piston disassembly and cleaning directions.
Before attempting to troubleshoot the valve or
disassemb
le the components
, check for the following:
must be flush with the stop/check cap) and that all
inlet and outlet shut-off valves are open
and that there are no cross-connectio ns or leaking
stop/check valves
temperature.
Be sure to close the appropriate shut-off valves prior
to disassembly of the valve and reopen the valves
after inspection and repair is complete.
Stop/Check Valve
Valve Seat
Stop/Check
Strainer