Series 6A Installation, Operation & Maintenance
Calibration & Commissioning
6A O & M : 16
Parameter Function Parameter Values Description
Turn Automatically sets 2) YAGL to 90
◦
WAY Used for linear actuators
LWAY Used for linear actuators
ncSt Used for a non-contacting position sensor on a part
turn actuator
-ncSt Used for a non-contacting position sensor on a part
turn actuator with a reverse direction of action
ncSL Used for linear actuators
1)YFCT Typeofpositionactuator
ncSLL Used for linear actuators
33
◦
2)YAGL Angleofrotation
90
◦
Used for linear actuators
3)YWAY RangeofStroke
Used for linear actuators
4)INITA Initialization(automatic)
NOINI | no/ ###.# | Strt Starts the automatic initialization process
5)INITM Initialization(manual)
NOINI | no/ ###.# | Strt Starts the manual initialization process
0 MA 0 MA only available for 3 to 4 wire connections.
6)SCUR Currentrangeofsetpoint
4 MA Factory setting.
riSE
7)SDIR SetpointSetup
FALL
Used to reverse the direction of the action of the
setpoint. Factory setting is “rise”
8)SPRA Setpointsplitrangestart
0.0 … 100.0 Used to limit the setpoint. Factory setting is “0”
9)SPRE Setpointsplitrangeend
0.0 … 100.0 Factory setting is “100”
10)TSUP SetpointrampOPEN
Auto / 0 … 400
11)TSDO SetpointrampCLOSED
0 … 400
Limits the speed of change of the effective setpoint.
Factory setting is “0”
1 – 25
1 – 33
1 – 50
Equal Percentage. Linearizes valve characteristics.
Factory setting is “Lin”
n1 – 25
n1 – 33
n1 – 50
Inverse equal percentage
12)SFCT SetpointFunction
FrEE Freely Adjustable
13)SLO
…33)SL20
SetpointTurningPoint
0.0 … 100.0 Assigns a flow metric to each setpoint interpolation
in units of 5%.
34)DEBA DeadZoneofClosed-
LoopController
Auto / .1 … 10.0 Adjust the dead zone to the requirements of the
control loop. Factory setting is “Auto”
35)YA Startofthemanipulated
variablelimit
0.0 … 100.0
36)YE Endofthemanipulated
variablelimit
0.0 … 100.0
Used to limit the mechanical actuator travel from
stop to stop to the configured values. “YE” must
always be larger than “YA”. Factory setting is “100”
MPOS Mechanical position from 0 to 100% between hard
stops.
37)YNRM Manipulatedvariable
scaling
FLOW Scaling from 0 to 100% over the range between
“YA” and “YE”
riSE
38)YDIR DirectionofManipulated
Variable
FALL
Used to set the direction of action of the display and
the position feedback Iy. Factory setting is “riSE”
No
uP
Do
39)YCLS Manipulatedvariabletight
closing
uP do
Used to move the valve into its seat with the
maximum force of the actuator. Factory setting is
“No”
40)YCDO Lowervaluefortight
closing
0.0 … 0.5 … 100% Factory setting is “0.5”