Series 6A Installation, Operation & Maintenance
Calibration & Commissioning
6A O & M : 16
Parameter Function Parameter Values Description
Turn Automatically sets 2) YAGL to 90
WAY Used for linear actuators
LWAY Used for linear actuators
ncSt Used for a non-contacting position sensor on a part
turn actuator
-ncSt Used for a non-contacting position sensor on a part
turn actuator with a reverse direction of action
ncSL Used for linear actuators
1)YFCT Typeofpositionactuator
ncSLL Used for linear actuators
33
2)YAGL Angleofrotation
90
Used for linear actuators
3)YWAY RangeofStroke
Used for linear actuators
4)INITA Initialization(automatic)
NOINI | no/ ###.# | Strt Starts the automatic initialization process
5)INITM Initialization(manual)
NOINI | no/ ###.# | Strt Starts the manual initialization process
0 MA 0 MA only available for 3 to 4 wire connections.
6)SCUR Currentrangeofsetpoint
4 MA Factory setting.
riSE
7)SDIR SetpointSetup
FALL
Used to reverse the direction of the action of the
setpoint. Factory setting is “rise”
8)SPRA Setpointsplitrangestart
0.0 … 100.0 Used to limit the setpoint. Factory setting is “0”
9)SPRE Setpointsplitrangeend
0.0 … 100.0 Factory setting is “100”
10)TSUP SetpointrampOPEN
Auto / 0 … 400
11)TSDO SetpointrampCLOSED
0 … 400
Limits the speed of change of the effective setpoint.
Factory setting is “0”
1 25
1 33
1 50
Equal Percentage. Linearizes valve characteristics.
Factory setting is “Lin”
n1 25
n1 33
n1 50
Inverse equal percentage
12)SFCT SetpointFunction
FrEE Freely Adjustable
13)SLO
33)SL20
SetpointTurningPoint
0.0 … 100.0 Assigns a flow metric to each setpoint interpolation
in units of 5%.
34)DEBA DeadZoneofClosed-
LoopController
Auto / .1 … 10.0 Adjust the dead zone to the requirements of the
control loop. Factory setting is “Auto”
35)YA Startofthemanipulated
variablelimit
0.0 … 100.0
36)YE Endofthemanipulated
variablelimit
0.0 … 100.0
Used to limit the mechanical actuator travel from
stop to stop to the configured values. “YE” must
always be larger than “YA”. Factory setting is “100”
MPOS Mechanical position from 0 to 100% between hard
stops.
37)YNRM Manipulatedvariable
scaling
FLOW Scaling from 0 to 100% over the range between
“YA” and “YE”
riSE
38)YDIR DirectionofManipulated
Variable
FALL
Used to set the direction of action of the display and
the position feedback Iy. Factory setting is “riSE”
No
uP
Do
39)YCLS Manipulatedvariabletight
closing
uP do
Used to move the valve into its seat with the
maximum force of the actuator. Factory setting is
“No”
40)YCDO Lowervaluefortight
closing
0.0 … 0.5 … 100% Factory setting is “0.5”

Other manuals for Bray 6A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bray 6A series and is the answer not in the manual?

Bray 6A series Specifications

General IconGeneral
BrandBray
Model6A series
CategoryValve Positioners
LanguageEnglish

Related product manuals