EasyManuals Logo

Brivis advance User Manual

Brivis advance
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #49 background imageLoading...
Page #49 background image
Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
49
Cooler Operation:
(cont.)
N-E5 Electronic Control Module Operation:
(cont.)
The N-E5 controller is fitted with an internal 8 Amp fuse to protect the PCB circuitry.
The 8 Amp fuse will protect the N-E5 controller from short circuit and/or high current
draw, on the following circuits:
Pump
Water inlet solenoid
Fan motor
PCB relays
Important Note:
The N-E5 internal 8 Amp fuse does not protect the control against short circuit on the
ServoSeal / drain valve motor circuit.
The N-E5 controller will maintain a minimum voltage on the output to the water inlet
solenoid in the OFF cycle.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Brivis advance and is the answer not in the manual?

Brivis advance Specifications

General IconGeneral
BrandBrivis
Modeladvance
CategoryFreezer
LanguageEnglish

Related product manuals